USCG Marine Safety Alert 05-12

Office of Commercial Vessel Compliance, Washington, DC
Monday, December 31, 2012

Pressure Switch Location for Fixed Fire Suppression Systems Where's yours located?


This safety alert addresses the location of fire suppression system pressure switches aboard vessels. These critical components sense the activation of the system and then electrically secures the ventilation systems operating in the protected space.  Securing the ventilation is essential in extinguishing a fire onboard a vessel. It assists in isolating the fire within the space, minimizes the introduction of additional oxygen to fuel the fire and prevents the loss of fire suppression agents from the space.


Recently, a vessel with an installed fixed CO2 fire suppression system, suffered extensive damage due to a fire that started in the engine room. During the firefighting efforts the crew reported that the engine room ventilation could not be secured.  A post casualty damage survey of the vessel revealed that the pressure switch used to secure the ventilation was located within the engine room. See the photograph of the damaged pressure switch at the right and new switch below.


Fixed CO2 systems on inspected/regulated vessels need to be type approved and installed in accordance with applicable regulations; 46 CFR 25.30-15, 46 CFR Subpart 76.15, 46 CFR Subpart 95.15, 46 CFR 118.410, etc.  These regulations require all controls and valves for the operation of the system to be outside the space protected, and notes they cannot be located in any space that might be cut off or made inaccessible in the event of fire in the protected spaces.  The Coast Guard considers pressure switches that are used in such systems a "control."


For Uninspected Towing Vessels, 46 CFR 25.30-15 (b) requires installation in accordance with 46 CFR Subpart 76.15 and reiterates the location requirements.


The Coast Guard strongly reminds Owners and Operators of vessels with installed fixed fire suppression systems to ensure that these switches are properly located aboard their vessels.  If the pressure switch or switches are located within the space being protected, they should be relocated by a properly trained fire suppression service technician.  Doing so will assist in ensuring system functionality and accessibility in the event of an emergency.  Failing to do so could have serious consequences to the vessel, its crew and the environment.

This safety alert is for informational purposes only and does not relieve any domestic or international safety, operational or material requirement. Developed by the Office of Commercial Vessel Compliance, Washington, DC.

Maritime Today

The Maritime Industry's original and most viewed E-News Service

Maritime Reporter November 2015 Digital Edition
FREE Maritime Reporter Subscription
Latest Maritime News    rss feeds

Marine Equipment

ACS Calls Krishnapatnam Port

HYUNDAI MERCHANT MARINE (HMM), the Korean conglomerate operating its ASIA CHENNAI SERVICE (ACS) made an ad hoc call at Krishnapatnam Port on November 26, 2015.   ACS

Cathelco Supply Equipment for Keppel Projects in Singapore

Press release -Cathelco have won orders to supply equipment for two projects which are being undertaken by Keppel yards in Singapore. The first is to provide marine

Barge Master Launches Fit-for-Purpose Gangway

Press release - Barge Master has announced the official launch of a motion compensated gangway after building a track record in motion compensated lifting. ‘The

Coast Guard

Nearly 100 Rescued after Batam Ferry Hits Trouble

Almost 100 people were rescued when a ferry sailing toward Singapore from the Indonesian island of Batam hit a floating object and reportedly started to sink, maritime officials said.

Rocket Debris Found Near Isles of Scilly

A piece of metal thought to be debris from an American space rocket was recovered from the sea off the Isles of Scilly.   The metal – a large section of alloy about 10 meters by 4 meters,

Passengers Transferred from Stranded Ferry

Passengers were transferred from Indonesia-registered Sea Prince after the ferry struck a floating object after leaving the Nongsapura ferry terminal in Batam late on November 29.

Maritime Safety

Australia, Japan Partner for Hydrodynamics Research

Australia and Japan have signed a cooperative research arrangement on marine hydrodynamics, the Chief Defence Scientist, Dr Alex Zelinsky, announced today.   “This

GOST Debuts New Technology at Workboat

GOST (Global Ocean Security Technologies), celebrating its 10th year as a world leader in marine security, tracking, monitoring and video surveillance systems,

BSEE Participates in Circumpolar Gap Analysis Workgroup

Bureau of Safety and Environmental Enforcement staff from the Oil Spill Preparedness Division attended an international workshop last month that focused on how

Government Update

Australia, Japan Partner for Hydrodynamics Research

Australia and Japan have signed a cooperative research arrangement on marine hydrodynamics, the Chief Defence Scientist, Dr Alex Zelinsky, announced today.   “This

ICS Backs Climate Change Deal

Press release - The global shipping industry, represented at the United Nations Conference in Paris by the International Chamber of Shipping (ICS), fully supports a global deal on climate change.

France-Corsica Ferry Operator SNCM's Takeover Gets EU Clearance

The European Commission has approved the takeover of troubled France-Corsica ferry operator SNCM by Corsican entrepreneur Patrick Rocca, according to a letter seen by Reuters on Tuesday.

Maritime Careers / Shipboard Positions Maritime Contracts Maritime Security Navigation Offshore Oil Pipelines Salvage Shipbuilding / Vessel Construction Sonar Winch
rss | archive | history | articles | privacy | contributors | top maritime news | about us | copyright | maritime magazines
maritime security news | shipbuilding news | maritime industry | shipping news | maritime reporting | workboats news | ship design | maritime business

Time taken: 0.1845 sec (5 req/sec)